Complementary
range

Acti 9

 
product name

Acti 9 C60H-DC

 
product or component type

Miniature circuit-breaker

 
device short name

C60H-DC

 
device application

Distribution

 
poles description

2P

 
number of protected poles

2

 
[In] rated current

6 A at 25 °C

 
network type

DC

 
trip unit technology

Thermal-magnetic

 
curve code

C

 
breaking capacity

Icu 20 kA at 220 V DC conforming to GB 14048.2
Icu 10 kA at 440 V DC conforming to EN 60947-2
Icu 10 kA at 440 V DC conforming to IEC 60947-2
Icu 6 kA at 500 V DC conforming to EN 60947-2
Icu 6 kA at 500 V DC conforming to IEC 60947-2
Icu 20 kA at 220 V DC conforming to IEC 60947-2
Icu 20 kA at 250 V DC conforming to GB 14048.2
Icu 20 kA at 250 V DC conforming to IEC 60947-2

 
suitability for isolation

Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2

 
Complementary
network frequency

50/60 Hz

 
[Ue] rated operational voltage

500 V DC

 
[Ics] rated service breaking capacity

15 kA 75 % x Icu at 220 V DC conforming to EN 60947-2
15 kA 75 % x Icu at 220 V DC conforming to IEC 60947-2
15 kA 75 % x Icu at 250 V DC conforming to EN 60947-2
15 kA 75 % x Icu at 250 V DC conforming to IEC 60947-2
4.5 kA 75 % x Icu at 500 V DC conforming to EN 60947-2
4.5 kA 75 % x Icu at 500 V DC conforming to IEC 60947-2
7.5 kA 75 % x Icu at 440 V DC conforming to EN 60947-2
7.5 kA 75 % x Icu at 440 V DC conforming to IEC 60947-2

 
[Ui] rated insulation voltage

500 V DC conforming to IEC 60947-2

 
[Uimp] rated impulse withstand voltage

6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2

 
contact position indicator

Yes

 
control type

Toggle

 
local signalling

ON/OFF indication

 
mounting mode

Fixed

 
mounting support

35 mm symmetrical DIN rail

 
comb busbar